(Summary description)The official website of Ren Yi was updated on July 8. Generally speaking, power cables cannot be exposed to water during production, and the inside of the cables must be dry. Because of the severe electric field voltage test, the water-infused cables cannot be shipped. Once the cable enters the water, under the action of the electric field, water tree aging will occur, leading to cable breakdown. When water penetrates the insulation, it will cause the cable to puncture and even explode to injure people.

Ren Yi Electric Encyclopedia: The reasons for water in the cable, these 10 preventive measures are too important.

(Summary description)The official website of Ren Yi was updated on July 8. Generally speaking, power cables cannot be exposed to water during production, and the inside of the cables must be dry. Because of the severe electric field voltage test, the water-infused cables cannot be shipped. Once the cable enters the water, under the action of the electric field, water tree aging will occur, leading to cable breakdown. When water penetrates the insulation, it will cause the cable to puncture and even explode to injure people.

  • Categories:Industry News
  • Author:Ren Yi
  • Origin:http://www.scrydq.com
  • Time of issue:2020-07-08 12:32
  • Views:
Information
The official website of Ren Yi was updated on July 8. Generally speaking, power cables cannot be exposed to water during production, and the inside of the cables must be dry. Because of the severe electric field voltage test, the water-infused cables cannot be shipped. Once the cable enters the water, under the action of the electric field, water tree aging will occur, leading to cable breakdown. When water penetrates the insulation, it will cause the cable to puncture and even explode to injure people.
 
1. Reasons for water in the cable
 
1. When storing
 
For the newly bought tube cable, both ends are sealed with plastic sealing sleeves, but after a section is used, the rest is wrapped in plastic paper, and the outside is tied with a rope. The airtightness is not good. Over time, water vapor will seep in. cable.
 
2. When laying cables
 
When the cable is laid, the cable head wrapped in plastic paper is sometimes immersed in water to allow water to enter the cable; when towing and threading, sometimes the outer sheath is broken.
 
3. After laying
 
After laying, the cable head was not made in time, so that the unsealed cable port was exposed to the air for a long time, or even immersed in water, causing a large amount of water vapor to enter the cable.
 
4. When the cable head is made
 
During the production of cable heads (including terminal heads and intermediate joints), due to the intention of the production staff, the cable ends sometimes slip into the cable well with water.
 
5. When the cable is running
 
During cable operation, when a fault such as a breakdown of the intermediate connector occurs, the water in the cable well will enter the cable along the gap; on the construction site, the cable will be damaged or punctured by external forces, and water will also enter the cable.
 
2. Treatment measures for cable ingress
 
After the cable enters the water, it is very difficult to dry it (such as using hot nitrogen to pressurize it), and generally there is no corresponding equipment. In actual operation, if the cable R6 enters the water, we just saw off the front end a few meters, if the entire cable has entered the water, we are undesirable. Therefore, the prevention of water ingress of cables should be based on prevention, and the following measures should be adopted:
 
1. The cable head should be sealed
 
The sawn off cable ends, whether stacked or laid, should be sealed with plastic (using a special cable gland) to prevent moisture infiltration.
 
2. Make the cable head in time
 
After the wire is laid, the cable head should be made in time.
 
3. When buying cables
 
Must choose a manufacturer with excellent quality. Since impurities and pores in the insulation are the starting point of water treeing, the quality of the cable is very important to prevent water tree aging.
 
4. Strengthen the management of cable head production process
 
Once the cable enters the water, the cable head is often the earlier breakdown phenomenon, so the wire head is made well to extend the overall life of the cable. For example, when the cable is peeling off the semiconductor layer, we cut a few vertically on the semiconductor layer, and then peel off the semiconductor like sugarcane peeling. However, when you use a knife to draw too deeply, it will damage the insulating layer and give opportunities for water trees. In addition, when soldering, because the power source cannot be found, the torch will be used to melt the solder directly. At this time, the flame will damage the copper shielding layer and the insulation layer. Therefore, this phenomenon must be eliminated. The correct way to configure UPS is because the soldering The time required is generally only 10min, and the power is only 500W.
 
5. Use cold shrinkable cable head
 
Cold-shrinkable silicone rubber cable accessories, simple and convenient to manufacture, no blowtorch, no solder. In addition, the silicone rubber cable accessories are elastic and tightly attached to the cable, which overcomes the shortcomings of heat-shrinkable materials (the heat-shrinkable material is not elastic, and there will be a gap between the cable body and the cable body during the thermal expansion and contraction of the cable. Provides convenience for the development of water trees).
 
6. Use cable branch box for long cables
 
For example, several long cables, each with a length of about 3km, for such cables, in addition to making intermediate joints, one or two cable branch boxes can also be used. Once one of the cables enters water, it will not spread to other sections. Cable, and it is also convenient to find in sections when the cable fails.
 
7. 8.7/10kV cables are used in the 10kV system
 
The insulation thickness of this grade cable is 4.5mm, while the insulation thickness of the 6/10kV grade cable is 3.4mm. Due to the increase of the cable insulation thickness, the field strength is reduced, which can prevent the aging of the water tree. At the same time, because the l0kV neutral point low-current grounding system is single-phase grounded, the cable must withstand 1.73 times the phase voltage and operate as required 2h, therefore, it is necessary to thicken the cable insulation.
 
8. Use PVC plastic double-wall corrugated pipe
 
The tube is corrosion-resistant, smooth inner wall, good strength and toughness, so when the cable is directly buried, it can greatly reduce the damage of the outer sheath of the cable.
 
9. Design of cable trench (pipe) and cable well
 
Due to the limitation of conditions, our cables are laid in the form of direct burial or cable trench, and most of them are directly buried. Our area belongs to the coastal rainy area, and there is water in the cable trench or cable well for many years. Since the depth of the cable trench or the cable well will exceed the depth of the sewer, drainage is very difficult, so in planning, coordination should be carried out to facilitate the drainage of the cable trench (well). If it is impossible to prevent the cable well from accumulating water, the intermediate joints in the cable well should be propped up with brackets. In addition, our district is a heavy chemical industry zone. There are many chemical companies in the zone. During inspections, it was found that some of the outer sheaths of the wires in the cable trenches near the chemical plant have been severely deformed. Therefore, the cable trenches near the chemical plant must have Complete drainage facilities. In addition, when designing the cable piping, try to be as straight as possible and reduce the elbow to make the cable easy to lay. At the same time, when the cable well is made, we divide it into a large cable well and a small cable well. The large cable well can be used to draw cables and coils. , Make the middle joint, and in the middle of the road, where it is not convenient to make a wire well but must have a corner, we changed it to a small cable well, which is only used to place the steering pulley when laying cables.
 
10. After the test cable head of the cable is made
 
Do a high-voltage DC leakage test before putting it into operation. After that, we only do a pre-test on the outgoing cables of the substation, and do not test other cables. This is because once the substation outlet cable fails, the short-circuit current will have a great impact on the substation equipment. Therefore, if there is a problem with the wire, it is necessary to strengthen the operation management and timely exchange. We believe that the post-processing of cable faults is the same trouble as the faulty cable found after the cable test: finding the fault point, and even replacing the cable. The shortcomings of the former are: unplanned power outages and short-circuit current impact. The advantage is: no test can extend the life of the cable (some cable tests are not ideal, but they can still run for a long time, and the DC test will increase cable damage. The possibility of wearing), the fault point is obvious and easy to find. The advantages and disadvantages of the latter are just the opposite of the former. Therefore, for cable users who do not do experiments, we focus on the reliability of their power supply. For example, the 10kV switch station that supplies power to users uses dual power supplies to realize dispatching automation. Once one incoming cable fails, it will immediately switch to the other. Cable power supply. In fact, in the new "Procedures for Preventive Tests of Power Equipment", cross-linked cables are no longer required to do DC withstand voltage tests at regular intervals, only the insulation resistance is measured, thus simplifying the preventive tests of cables.
 
 
 
Sichuan Renyi Electric Co., Ltd. is registered under the name of Ren Yi, a senior technician for substation maintenance, and uses scientific research, knowledge innovation, publicity, promotion, and teaching that the temperature of electrical contacts (connectors) is lower than the temperature of its conductors (wires). The theory and technology of "thermal electrical contacts" produces and sells electrical equipment with registered trademarks that do not overheat electrical contacts (joints). Patented products are integrated.
Today

Today talks about: Solving various electrical disasters from the source of electricity -

Mount Everest on Electricity [Today's Talk]: The difference between "heating" and "overheating"; the three stages of "Electrical Contact Overheating":
2019-11-18
119

119 Safety and firefighting must be done practically. "Superconductivity" cannot solve man-made disasters such as electrical fires!

119 Safety and firefighting must be done practically. "Superconductivity" cannot solve man-made disasters such as electrical fires!
2019-11-09
Pay

Pay special attention to the power safety revolution forum, and Mount Everest discusses electricity-to solve the mystery of a century of electrical disasters in the world of man-made disasters! Solve and eradicate the global ...

Pay special attention to the power safety revolution forum, Mount Everest on electricity-to solve the mystery of a century of electrical disasters and man-made disasters in the world! Solve and eradicate the global problems of air disasters, fires and spontaneous combustion from the source of electricity! Look at the Tianbang in Nanchong and Niuhuang Wan in Chengdu, one of China's ribs. In decades of production practice, how to continuously explore, repeatedly test, reverse thinking, gradually improve, and independently innovative scientific and technological achievements. This intellectual property, which is unique to China in the world, is completely independent, and is sent to the country free of charge. Take a look at the folk "Lao Lai Le", defying academic authority, summoning conscience, calling for revolution, and creating a unique world, how to overcome electrical disasters and man-made disasters, this worldwide problem! Special reminder: This is just advice and advice, not an advertisement. If you believe in an advertisement, or listen to advice and advice, it's up to you. This is a matter of folk merit. Advice and advice do not ask for compensation, do not ask for likes, do not want to be Internet celebrities, improper celebrities, just because of professional responsibility, just because I see someone killed by an electrical disaster, my conscience is also disturbed. WeChat friends, and their respective media think this is positive energy and a good thing. You can be busy reprinting and disseminating the original text (the original propaganda and promotion are not for profit, and I am responsible for mistakes). If the national media wants to propagate and disseminate, first declare: this is not advertising! Without money, who can do it?
2019-11-08
Special

Special attention should be paid to national power safety in summer

History, tradition, and habit believe that: poor contact; weak electrical contacts (joints); electrical contacts whose temperature is higher than (exceeds) the temperature of its conductor (line). The theoretical concept of "electrical contacts overheating" is wrong! It is believed that oxidative corrosion (chemical, electrical corrosion) caused the "electrical contact overheating", which reverses the causality! Please go to the China Renyi Electric Platform (challenge) for academic discussion and debate!
2015-07-23

CONTACT US

 

Email: 577538063@qq.com

Phone:+86 13438175710

ADD

 

128 Hongyang East Road, Qingbaijiang District, Chengdu

CHENGDU BRANCH

 

Room 3101, Tower 2, Raffles City, Wuhou

District, Chengdu,PR China

+86 13438175710
577538063@qq.com

 Copyright © 2022 Sichuan Renyi Electric Co., Ltd. 蜀ICP备12025125号  Powered by:www.300.cn   SEO